Home | Contact | Sitemap | Search
UnternehmenFüllstandmesstechnikEnergieversorgungAuftragsfertigung
Product overview
Level Switches
Concept
Standard Range
Industrial Range
Plastic Range
Accessories
Pneumatic Controlers
Vertical switches
Optoelectronic Level Sensors (Senlux)
Float Level Switches (GEMS)
Float Switches (KARI)
Level Indicators (WEKA)
Approvals
Order form
Contact
Distributors
Documentations
News

  Vertical switches

Level switch - For vertical mounting
Type A 01 140 to A 01 141
 

Type A 01 140 and A 01 141
Vertical mounting, for use as limit/alarm function or as pump control (2-point control).
Nominal pressurePN 16, max 16 bar to 300°C
Operating temperature0 to 300°C
Ambient temperature0 to 70°C
Density of liquid min.
pump control0.45 kg/dm³
alarm0.30 kg/dm³
Operating differential
A 01 14012 to 1340 mm
A 01 14112 to 2840 mm
Wetside materialStainless steel (CrNiMo)
Flange materialStainless steel (CrNiMo)
Switch housing materialSea-water resistant die-cast aluminium
Flange dimensions92 x 92 mm (hole circle: 92 mm)
Switch elementMicroswitch (SPDT), silver contacts
Switch rating250 VAC, 5 A 30 VDC, 5 A
EnclosureIP 65
Weight
A 01 140ca. 2,5 kg
A 01 141ca. 2,7 kg
 



Top mounted level switches type A 01 140, A 01 141 (LTDS02E)
(PDF, 2 pages, 150 kByte)
> download in english
> download other languages
> all documentations

Contact

Adjustment of the operating differential
The required operating differential is attained by fixing stop collars on the rod. The alarm function or pump control is set by means of the counterweight.

Zum Seitenanfang